Print

Designing a 500 kVA, 60Hz, K-Factor, three phase dry transformer with cooling channels?

General Information

Technical Specification

Input voltage 3 x 480V, delta
Output voltage 3 x 208/120V, star
Output power 500kVA, K-Factor=20, continuous operating mode
Frequency 60Hz
Ambient temperature 40°C, in a cabinet
Temperature rise Max. 120°K, insulation class H
°Short-circuit voltage 4-5%
Steel&core M6, not annealed, strips for alternated stacking (90°)

Creating Input

There are 4 input screens to set the input parameters for the designing of a transformer:

  • Winding parameters per limb
  • Core
  • Environment
  • Other parameters

and 3 screens for selection and set up of material:

  • wires
  • steels
  • cores.

Windings parameters per limb

Windings parameters per limb

Primary

The primary is created with 2 windings connected in series . The sine wave input voltage is 480V (240V per winding).

There is no duty cycle operation mode and there are no sectors.

Note that a 500kVA transformer for K-factor=20 and the short-circuit voltage 5% can be optimal designed and manufactured only with litz wire. The round wires within the litz are not insulated but in transposition.

The first winding has the thermal contact with the center leg of the core within the core window via 0.1" tube thickness and 0.1" air gap (stomach).

All other surfaces of the primary are cooled via the cooling channels of 0.6" (inside of the core window) and 0.8" (outside of the core window).

The space between the yoke and the primary windings is 1.2" With the eddy current losses factor (RacRdc) 1.1 and 1.25 shell be limited the number of the round wires per litz.

Primary

Secondary

The secondary is created with 2 windings connected in parallel . The sine wave output voltage is 120V.

The rms current per winding is 696Arms. Normally there is no explicit information about the current harmonics in a K-factor transformers. The designer has to create a combination of the first current harmonic and 7. current harmonic in order to satisfy the following conditions:

I1^2 + I7^2 = Irms^2

1^1*I1^2 + 7^2*I7^2 = K-factor* Irms^2

For Irms = 696Arms and K-factor = 20 the calculated current harmonics I1 and I7 are:

I1= 540Arms

I7 = 437Arms

Also there is no duty cycle operation mode on the secondary side.

In order to avoid the circulating current between 2 parallel connected secondary windings each of them is created with 2 cross connected sectors.

Once again, a 500kVA transformer for K-factor = 20 and the short-circuit voltage 5% can be optimal designed and manufactured only with litz wire. With the eddy current losses factor

(RacRdc) 1.1 and 1.25 the number of the round wires per litz shall be limited. Note that at this point of design you can not prescribe the wire size. You can select only the wire family which the program has to use in order to select the suitable wires for your application.

The first secondary winding is cooled via the cooling channels of 0.6" (inside of the core window) and 0.8" (outside of the core window). The second secondary winding has only two

0.8" cooling channels outside of the core window. It is better cooled than the first secondarywinding and therefore it is in a good thermal connection within the core window with the first secondary winding.

The space between the yoke and the secondary windings is 1.2"

Core

On this input screen you can:

  • select and manipulate the selected steel M6, 14mil
  • set the operating induction (1.65T) and the frequency (60Hz)
  • select the core assembly
  • and prescribe the core selection.
Core

The core was created by program and by the designer in order to satisfy the following conditions:

  • Ucc=5%
  • Optimal price and weight
Core

Normally for this application you use M6, 14mil, non annealed after stamping, grain oriented strips.

Core

Environment

The cooling medium is air with the ambient temperature 40°C. The cooling factors for the convection and the emission are set to 80% because the transformer will be placed in a cabinet.

The cooling surface of the core is increased by using 4 L-brackets on the core.

The impregnation is practically "dry" because there is only 10% varnish (90% air) in the windings and in all the gaps between the insulations and the layers of the windings

Environment

Other...

Other...

The selected criterion of the design is the temperature rise of 120°K for insulation class H. The oval space between the first winding and the tube (stomach), all gaps between the insulation, the windings and the varnish fill factor of the windings play very important roll from the thermal point of view.

Output

The first step is the presentation of the output screen DIAGNOSIS: it is the summery of the most important calculated parameters of your transformer.

Output

Note that the program uses the numerical calculation of the magnetic fields and the temperature rises. Due to this technology the calculations of the eddy current losses, the steel losses, the

short-circuit voltage, the circulating current and the transposition are very powerful.

In the following picture are presented the magnetic field outside of the core window.

Finally here are 4 printed pages with all the results of the design

Input

Input

Core

Core p>Windings

Windings p>Nominal operating mode

Nominal operating mode

Test Mode

If you are not satisfied with the solution made by the program you can switch into the Test Mode and change your transformer manually:

  • Turns
  • Wire size
  • Material (Cu or Al)
  • Number parallel connected wires and their order in strand
  • Cooling channels and insulations
  • Margin
  • Steel
  • Technology parameter (impregnation, gaps,...)

and then you can set it under an operation mode changing:

  • Input voltage
  • Frequency
  • Loads and their K-factors
  • Duty cycle of each winding
  • Ambient temperature
  • Air flow

Note that the program could not create full layer windings at the prescribed temperature rise of 120°K.

In order to get the full layer windings you have to select the wire size in the litz and the number in parallel connected wires manually.

Impregnation

Let us now change some technology parameters of this transformer:

Impregnation

In the following table you can compare the temperature rise of our "dry" transformer and the full impregnated (no air in the windings, the gaps and the stomach) version.

  Core °K Primary1 °K Primary2 °K Secondary1 °K Secondary2 °K
Current version: 10% varnish 105 114 113 121 117
New version: 100% varnish 105 109 109 113 109

Core assembly

If you want to use 45°core assembly with the annealed M6 strips then:

Core-assembly
  Core °K Primary1 °K Primary2 °K Secondary1 °K Secondary2 °K
Current version: 90° core assembly,non annealed strips 105 114 113 121 117
New version: 45° core assembly, annealed strips 90 107 109 120 116

Impregnation

In the following table you can compare the temperature rise of our "dry" transformer and the full impregnated (no air in the windings, the gaps and the stomach) version.

  Core °K Primary1 °K Primary2 °K Secondary1 °K Secondary2 °K
Current version: in the cabinet 105 114 113 121 117
New version: no cabinet 96 104 104 109 103